9.2.7 Replace the fan unit for the heat sink
Inverters, frame sizes FSA … FSF have a fan unit for the heat sink. The fan unit for the heat
sink is located at the lower side of the inverter.
When must the fan unit be replaced?
A defective fan unit in operation results in an overtemperature condition of the inverter. For
example, the following messages indicate that the fan unit is defective:
A05002 (air intake overtemperature)
A05004 (rectifier overtemperature)
F30004 (heat sink overtemperature)
F30024 (temperature model overtemperature)
F30025 (chip overtemperature)
F30035 (air intake overtemperature)
F30037 (rectifier overtemperature)
Remove fan unit, FSA ... FSC
/RFNLQJODWFKHV/RFNLQJODWFKHV
3RZHU
FRQQHFWRU
3RZHU
FRQQHFWRU
)UDPH6L]H$)UDPH6L]H&
Figure 9-1 Remove fan unit for heat sink
Corrective maintenance
9.2 Replacing inverter components
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 385