10.8 Restrictions for special ambient conditions
Permissible line supplies dependent on the installation altitude
For installation altitudes ≤ 2000 m above sea level, it is permissible to connect the inverter
to any of the line supplies that are specified for it.
For installation altitudes 2000 m ... 4000 m above sea level, the following applies:
Connection to a TN line system with grounded neutral point is permissible.
TN systems with grounded line conductor are not permitted.
The TN line system with grounded neutral point can also be supplied using an isolation
transformer.
The phase-to-phase voltage does not have to be reduced.
Current derating depending on the installation altitude
The permissible inverter output current is reduced above an installation altitude of 1000 m.
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@





Figure 10-2 Current derating depending on the installation altitude, FSAA … FSC
,QVWDOODWLRQDOWLWXGH>P@
2XWSXWFXUUHQW
>@







Figure 10-3 Current derating depending on the installation altitude, FSD … FSF
Technical data
10.8 Restrictions for special ambient conditions
SINAMICS G120C converter
414 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF