EasyManua.ls Logo

Siemens SINAMICS G120C USS/MB - Invert Setpoint

Siemens SINAMICS G120C USS/MB
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.17.2 Invert setpoint
The inverter provides an option to invert the setpoint sign using a bit. As an example, the
setpoint inversion is shown through a digital input.

S

[
\
[
\
W
\\[[

To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal,
e.g. digital input 1.
Table 6-40 Application example for inverting the setpoint
Parameter Remark
p1113 Setpoint inversion (factory setting depends on the inverter)
p1113 = 722.1 Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Inverter inverts the setpoint.
p1113 = 2090.11 Invert setpoint via control word 1, bit 11.
Advanced commissioning
6.17 Setpoint calculation
SINAMICS G120C converter
244 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF