Select the application:
VEC STD: In all applications, which do not fit the other setting options.
PUMP FAN: Applications involving pumps and fans
SLVC 0HZ: Applications with short ramp-up and ramp-down times. However, this setting
is not suitable for hoisting gear and cranes/lifting gear.
PUMP 0HZ: Setting only for steady-state operation with slow speed changes. We
recommend setting VEC STD if load surges in operation cannot be ruled out.
Select the control mode:
VF LIN: U/f control with linear characteristic
VF LIN F: Flux current control (FCC)
VF QUAD: U/f control with square-law characteristic
SPD N EN: Encoderless vector control
Select a suitable control mode
Control mode U/f control or flux current control (FCC) Encoderless vector control
Motors that can be
operated
Induction motors Induction and synchronous motors
Application exam‐
ples
Pumps, fans, and compressors with flow
characteristic
Wet or dry blasting technology
Mills, mixers, kneaders, crushers, agitators
Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
Basic spindles
Pumps and compressors with displacement
machines
Rotary furnaces
Extruder
Centrifuges
3
7(&$33/
3
&75/02'
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120C converter
130 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF