[11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
[12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
Calculating the motor parameters: Select "Complete calculation".
Set the check mark for "RAM to ROM (save data in the drive)" to save your data in the inverter
so that it is not lost when the power fails.
Select "Finish".
Figure 5-16 Exiting quick commissioning in STARTER
Figure 5-17 Exiting quick commissioning in Startdrive
You have completed quick commissioning.
Select a suitable control mode
Control mode U/f control or flux current control (FCC) Encoderless vector control
Motors that can be
operated
Induction motors Induction and synchronous motors
Application exam‐
ples
Pumps, fans, and compressors with flow
characteristic
Wet or dry blasting technology
Mills, mixers, kneaders, crushers, agitators
Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
Basic spindles
Pumps and compressors with displacement
machines
Rotary furnaces
Extruder
Centrifuges
Commissioning
5.5 Quick commissioning with a PC
SINAMICS G120C converter
146 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF