Parameter for Vdc_max control
The parameters differ depending on the motor control mode.
Parameter for V/
f control
Parameter for
vector control
Description
p1280 = 1 p1240 = 1 VDC controller configuration(factory setting: 1)
1: VDC controller is enabled
r1282 r1242 Vdc_max control switch-on level
DC-link voltage value above which the Vdc_max control is activa‐
ted
p1283 p1243 Vdc_max control dynamic factor (factory setting: 100 %) Scaling
closed-loop control parameters p1290, p1291 and p1292
p1294 p1254 Vdc_max control automatic ON level sensing(factory setting, de‐
pendent on the Power Module)
0: Automatic detection disabled
1: Automatic detection enabled
p0210 p0210 Unit supply voltage
If p1254 or p1294 = 0, the inverter uses this parameter to calculate
the switch-in thresholds of the Vdc_max control.
Set this parameter to the actual value of the input voltage.
For more information about this function, see the List Manual (function diagrams 6320 and
6220).