Table 6-58 Parameters for switching the drive data sets:
Parameter Description
p0820 Drive data set selection DDS
p0826 Motor changeover, motor number
r0051 Displaying the number of the DDS that is currently effective
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the Parameter Manual.
Note
You can only switch over the motor data of the drive data sets in the "ready for operation" state
with the motor switched-off. The switchover time is approx. 50 ms.
If you do not switch over the motor data together with the drive data sets (i.e. same motor
number in p0826), then the drive data sets can also be switched over in operation.
Table 6-59 Parameters for copying the drive data sets
Parameter Description
p0819[0] Source drive data set
p0819[1] Target drive data set
p0819[2] = 1 Start copy operation
For more information, see the List Manual (the parameter list and function diagram 8565).
Advanced commissioning
6.32 Switchover between different settings
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 319