Parameter Description
p2126[0 … 19] Setting the fault number for the acknowledgement mode
Selection of the faults for which the acknowledgement type should be changed.
You can modify the acknowledgement type for up to 20 different fault codes.
p2127[0 … 19] Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgement after removing the fault cause
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
Alarms, faults and system messages
8.4 Faults, alarm buffer and alarm history
SINAMICS G120C converter
360 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF