Removing the fan unit, FSD … FSF
Procedure
Proceed as follows to remove the fan unit:
1. Switch off the inverter power supply.
WARNING
Electric shock due to residual charge in power components
After the power supply has been switched off, it takes up to 5 min. until the capacitors in
the inverter have discharged so that the remaining charge is at a non-hazardous level.
Check the voltage at the inverter connections before you carry out any installation work.
2. Remove the fan unit from the Power Module in steps and as shown in the diagram.
Use a screwdriver if necessary.
OLIW
3. Additionally for PT devices:
Remove the interior fan as shown below.


Corrective maintenance
9.2 Replacing inverter components
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 387