Article No. without filter
Article No. with filter
6SL3210-1KE24-4U . 1
6SL3210-1KE24-4A . 1
6SL3210-1KE26-0U . 1
6SL3210-1KE26-0A . 1
6SL3210-1KE27-0U . 1
6SL3210-1KE27-0A . 1
Power loss without filter 647 W 927 W 1.024 kW
Required cooling air flow 55 l/s 55 l/s 55 l/s
Weight with filter 19 kg 19 kg 20 kg
Weight without filter 17 kg 17 kg 18 kg
Table 10-9 Frame size D, 3 AC 380 V … 480 V, +10 %, -20 %
Article no. without filter
Article no. with filter
6SL3210-1KE28-4U . 1
6SL3210-1KE28-4A . 1
LO base load power 45 kW
LO base load input current 76 A
LO base load output current 82.5 A
HO base load power 37 kW
HO base load input current 69 A
HO base load output current 68 A
Power loss with filter 1.304 kW
Power loss without filter 1.291 kW
Required cooling air flow 55 l/s
Weight with filter 20 kg
Weight without filter 18 kg
Table 10-10 Frame size E, 3 AC 380 V … 480 V, +10 %, -20 %
Article no. without filter
Article no. with filter
6SL3210-1KE31-1U . 1
6SL3210-1KE31-1A . 1
LO base load power 55 kW
LO base load input current 96 A
LO base load output current 103 A
HO base load power 45 kW
HO base load input current 85 A
HO base load output current 83 A
Power loss with filter 1.476 kW
Power loss without filter 1.466 kW
Required cooling air flow 83 l/s
Weight with filter 29 kg
Weight without filter 27 kg
Technical data
10.5 Technical data dependent on the power
SINAMICS G120C converter
410 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF