Status
3. Select STO
3.1. Select STO while the motor is running.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2.
Check the following:
When controlled via
PROFIsafe
When controlled via a fail-
safe F-DI digital input
When controlled via
STO_A and STO_B ter‐
minals on a PM240‑2 or
PM240P‑2 Power Mod‐
ule
The inverter signals
the following:
"STO selection via
PROFIsafe"
(r9772.20 = 1)
The inverter signals
the following:
"STO Selection via
terminal"
(r9772.17 = 1)
The inverter signals
the following:
"STO Selection via
terminal on Power
Module"
(r9772.25 = 1)
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
4. Deselect STO
4.1. Deselect STO.
4.2. Check the following:
STO is not active (r9773.1 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
You have performed the acceptance test of the STO function.
Appendix
A.6 Acceptance test for the safety function
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 455