Connecting the line supply and motor, frame size FSF
Figure 4-23 Connecting the line supply and motor, FSF
Remove the lower connection covers.
Use side cutters or a fine saw blade to make openings in the cover for the cables.
You must re-attach the covers in order to re-establish the touch protection of the inverter after
the cables have been connected.
Connecting the braking resistor, frame sizes FSD … FSF
We recommend mounting the shield plate. The shield plate is not included in the scope of
delivery of the inverter.
Spare parts (Page 383)
Procedure
To connect a braking resistor, proceed as follows:
1. Remove the upper inverter cover.
2. Release the two braking resistor terminals.
3. Remove the seal together with the connection cover upwards away from the inverter.


Installing
4.8 Connect the line supply, motor and braking resistor
SINAMICS G120C converter
72 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF