Operation 11/03
SINAMICS G150
6-20 Operating Manual
6.3.2 Analog Inputs
Description
The customer terminal block features two analog inputs for specifying setpoints via
current or voltage signals. In the factory setting, analog input 0 (terminal X521:1/2)
is used as the current input.
Prerequisite
p1070 = r4055[00]
Main setpoint is specified by analog input 0
<MENU> - <parameterization> - <all parameters> - Select
p1070 and set to r4055 - Select index [00]
Proposed Connection Assignment
4
3
2
1
5
6
=
~
~
=
M
~
X521
~
~
8
7
S5.0
M
+
1
N10
M
P10
AI 1-
AI 1+
AI 0+
AI 0-
DI 4
4
3
2
1
5
6
X520
M
M1
DI 3
DI 2
DI 1
DI 0
1
X530
X540
-A10 (CU 320)
-A60 (TM31)
ON/OFF1
Fault ack.
PROFIBUS/
terminal block
1: Terminal
block
user wiring
20 mA = n max
(p2000)
Fig. 6-8 Proposed connection assignment