11/03 Technical Data
SINAMICS G150
Operating Manual
12-5
12.3.1 Cabinet Unit Version A, 380 V – 480 V
Table 12-6 Version A, 380 V – 480 V, part 1
Category Unit
Order no. 6SL3710- 1GE32-1AA0 1GE32-6AA0 1GE33-1AA0
Rated motor output kW 110 132 160
Rated connection voltage V 3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current A 239 294 348
Rated output current A 210 260 310
Base load current A 205 250 302
Power loss kW 2.9 3.8 4.4
Cooling air requirement m³/s 0.17 0.23 0.36
Sound pressure level at 50/60
Hz
dB(A) 67/68 69/73 69/73
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 70
2 x (000)
4 x 240
4 x (600)
M12 (2 holes)
2 x 95
2 x (4/0)
4 x 240
4 x (600)
M12 (2 holes)
2 x 120
2 x (300)
4 x 240
4 x (600)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 70
2 x (000)
2 x 150
2 x (400)
M12 (2 holes)
2 x 95
2 x (4/0)
2 x 150
2 x (400)
M12 (2 holes)
2 x 120
2 x (300)
2 x 150
2 x (400)
M12 (2 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard
version)
kg 320 320 390
Dimensions (w x h x d) mm 800 x 2000 x 600 800 x 2000 x 600 800 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 252
315
2
3NE1 230-2
315
1
3NA3 254
355
2
3NE1 231-2
350
2
3NA3 365
500
3
3NE1 334-2
500
2