10.5.2 List of Faults and Alarms
Table 10-4 List of Faults and Alarms
F1000 Internal software error
Reaction: OFF2
Cause: An internal software error has occurred.
Fault value
(r0949):
To be diagnosed by Siemens only.
Remedy: - POWER ON for all components (switch off/on).
- Upgrade firmware.
- Contact hotline.
- Replace control unit.
Acknowl.: POWER ON
F1005 Firmware download DRIVE-CLiQ component failed
Reaction: NONE
Cause: Firmware download to a DRIVE-CLiQ component failed.
Fault value
(r0949):
011: The DRIVE-CliQ component has recognized a checksum error.
015: The content of the firmware file is not accepted by the selected DRIVE-CliQ
component.
140: The firmware file for the DRIVE-CliQ component does not exist on the CompactFlash
card.
156: The component with the specified component number does not exist.
Other values:
To be diagnosed by Siemens only.
Remedy: - Check the selected component number (p7828).
- Store the appropriate firmware file for download in the /siemens/sinamics/code/sac/
directory.
Acknowl.: Immediate
F1010 Unknown drive type
Reaction: NONE
Cause: Unknown drive type found.
Fault value
(r0949):
Drive object number
Remedy: Check EEPROM data of the drive objects.
Acknowl.: Immediate
F1030 Monitoring master control: Sign-of-life failure PC
Reaction: OFF1
Cause: No signs-of-life were received during active PC control priority within the monitoring time.
Control priority has been returned to the active BICO interconnection.
Remedy: Increase the monitoring time on the PC/AOP or switch it off.
WARNING:
The monitoring time must be as short as possible. A long monitoring time results in a
delayed reaction if communication fails!
Acknowl.: Immediate
F1040 You must save your parameter settings and perform a POWER ON
Reaction: OFF2
Cause: A parameter which requires the system to reboot, e.g. p0110, has been changed in the drive
system, e. g. p0110.
Remedy: - Save parameters (p0971/p0977)
- Perform POWER ON for all components (deactivate/activate)
Acknowl.: POWER ON
F1041 You must save your parameter settings