Commissioning 11/03
SINAMICS G150
5-4 Operating Manual
5.3.2 Basic Commissioning
Entering the Motor Data
During initial commissioning, you have to enter motor data using the operator
panel. Use the data shown on the motor type plate.
p0305
p0311p0307p0310
p0304
S
3 ~MOT. 1LA8 315-4PM80 315 No N- 1107840010001/2002 IMB3
V
400
690
Hz
50
A
405
235
kW
235
cosϕ
0,87
1/min
1485
IA/IN TE s Certif.
No
IP
55
Rotor SQU.CAGE KL 13 EN/IEC 60034-1 Gew/Wt 1,3 t
NMAX=3000 1/MIN
MADE IN GERMANY
DEW0233
p0308
Fig. 5-3 Example of a motor type plate
Table 5-4 Motor data
Parameter no. Values Unit
System of units for line frequency and entering
motor data
p0100 0
1
IEC [50 Hz / kW]
NEMA [60 Hz / hp]
Motor:
Rated voltage
Rated current
Rated output
Rated power factor Cos Ï• (at p0100 = 0 only)
Rated efficiency η (at p0100 = 1 only)
Rated frequency
Rated speed
p0304
p0305
p0307
p0308
p0309
p0310
p0311
[V]
[A]
[kW] / [hp]
[%]
[Hz]
[min-1] / [rpm]