7.2.2 Minimum Speed
Description
Specifying a minimum speed allows you to disable a specific range about speed 0
1/min for stationary operation.
Signal Flow Diagram
Minimum speed
Minimum speed
p1080
-1
x
y
x
y
nSet_afterSkip
r1112
Setp_after_Lim
r1114
Suppress. speed
Fig. 7-1 Signal flow diagram: Minimum speed
Setting Parameters
Setting range: 0.000 ... 19500.000 1/min
p1080 Minimum speed
Factory setting: 0.000 1/min
Setting parameter for the minimum speed. This speed is not undershot during operation.
r1112
Speed setpoint after minimum limit Unit: 1/min