11/03 Operation
SINAMICS G150
Operating Manual
6-17
Current fault in: 33463512
F7011 Drv: Motor Overtemp.
Help Old Back Ack.
F2F1 F3 F4 F5
Drv: Motor Overtemp.
Fault value: 00000000 00000000H
Cause:
Motor temperature has reached the
fault threshold parameterized in
(p0605).
Remedy:
Back  
F2F1 F3 F4 F5
F1
Fig. 6-6 Fault screen
Alarm memory Status
A7850 External warning 1
A7910 Drv: Motor Overtemp. active
A7852 External warning 3
Help î™” Delete Back upd.
F2F1 F3 F4 F5
Antr: Motor Übertemp.
AlarmVal: 00000000 00000000(hex)
Cause:
Motor temperature has exceeded the
alarm threshold parameterized in
p0604.
The reaction set in p0610 is
Back  
F2F1 F3 F4 F5
F1
F5
Fig. 6-7 Alarm screen
6.2.5 Saving the Parameters Permanently
Description
If parameters have been changed on the operator panel (press OK in the
Parameter Editor to confirm), the new values are initially stored in a volatile
memory (RAM). An "S" flashes in the top right of the display until they are saved to
a permanent memory. This indicates that at least 1 parameter has been changed
and not yet stored permanently.
Two methods are available for permanently saving parameters that have been
changed:
• Call up the Help function from any screen and press F4 EEPROM
• When confirming a parameter setting with OK, press the OK key for > 1s. The
system displays a message asking you whether the setting is to be saved in the
EEPROM.
If you press "Yes", the system saves the setting in the EEPROM. If you press
"No", the setting is not saved permanently and the "S" starts flashing.
In both cases,
all changes that have not yet been saved permanently are stored in
the EEPROM.