Technical Data 11/03
SINAMICS G150
12-2 Operating Manual
12.2 General Data
Table 12-1 General technical data
Electrical data
Power frequency 47 Hz to 63 Hz
Output frequency 0 Hz to 83 Hz
Power factor
Fundamental mode
Total
≥ 0.98
0.93 to 0.96
Converter efficiency > 98 %
Switching at input Once every 3 minutes
Mechanical data
Degree of protection IP 20 (higher degrees of protection up to IP 54 optional)
Type of cooling Forced air cooling
Sound pressure level ≤ 72 dB(A) at 50 Hz line frequency
≤ 75 dB(A) at 60 Hz line frequency
Shock-hazard protection BGV A2
Cabinet system Rittal TS 8, doors with double-barb lock
Paint finish RAL 7035 (indoor requirements)
Compliance with standards
Standards EN 60 146-1, EN 61 800-2, EN 61 800-3, EN 50 178, EN 60 204-1, EN 60 529
CE marking According to EMC directive No. 89/336/EC and low voltage directive No. 73/23/EC
Electromagnetic
compatibility
RI suppression filter according to EN 55 011, Class A1, available as option (for
TN/TT systems)
RI suppression According to EMC product standard for variable-speed drives EN 61 800-3
(restricted distribution)
Ambient conditions
Operation Storage Transport
Ambient temperature 0 °C to +40 °C
Up to + 50 °C with
derating
-25 °C to +55 °C -25 °C to +70 °C
Above –40 °C for 24 hours
Humidity range
(non-condensing)
Corresponds to class
5 % to 95 %
3K3 to IEC 60 721-3-3
5 % to 95 %
1K4 to IEC 60 721-3-1
5 % to 95 % at 40 °C
2K3 to IEC 60 721-3-2
Site altitude Up to 2000 m above sea level without derating,
> 2000 m above sea level with derating, see Section 12.2.1
Mechanical stability
Vibratory load:
Deflection
Acceleration
Corresponds to class
0.075 mm at 10 Hz - 58
Hz
10 m/s² at > 58 Hz - 200
Hz
-
1.5 mm at 5 Hz - 9 Hz
5 m/s² at > 9 Hz - 200 Hz
1M2 to IEC 60 721-3-1
3.5 mm at 5 Hz - 9 Hz
10 m/s² at > 9 Hz - 200 Hz
2M2 to IEC 60 721-3-2
Shock load:
Acceleration
Corresponds to class
100 m/s² at 11 ms
3M4 to IEC 60 721-3-3
40 m/s² at 22 ms
1M2 to IEC 60 721-3-1
100 m/s² at 11 ms
2M2 to IEC 60 721-3-2