11/03 Maintenance and Servicing
SINAMICS G150
Operating Manual
11-11
11.7 Using a Replacement CompactFlash Card
Description
When you replace a flash card with a new card from Siemens, you have to activate
the cabinet settings before carrying out commissioning.
Procedure
• When you switch the system on for the first time, the message "Configuration?"
appears on the operator panel.
Confirm with "YES" (soft key).
• After initialization, the initial motor commissioning screen is displayed. Before
you start commissioning, however, you first have to load the cabinet factory
setting.
• Call up the main menu.
• Set the "Expert" access level.
• MENU – Parameterization – All Parameters
• p0009 = 30
• p0976 = 20, 21, or 22
– 380 V - 480 V, 110 kW - 250 kW: p0976 = 20
– 380 V - 480 V, 315 kW - 560 kW: p0976 = 21
– 660 V - 690 V, 75 kW - 800 kW: p0976 = 22
• When the parameter list is displayed again, the basic settings are loaded
(ignore any faults).
Switch on the power and start commissioning as normal.