EasyManua.ls Logo

Siemens SINAMICS G150 - Output Terminals; Power Connections; Connection Cross-Sections and Cable Lengths

Siemens SINAMICS G150
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation 11/03
SINAMICS G150
4-10 Operating Manual
4.6 Power Connections
WARNING
• Swapping the input and output terminals can destroy the cabinet unit!
• Swapping or short-circuiting the DC link terminals can destroy the cabinet unit!
• The contactor and relay operating coils that are connected to the same supply
network as the cabinet unit or are located near the cabinet unit must be
connected to overvoltage limiters (e.g. RC elements).
• The cabinet unit must not be operated via a residual current operated device
(DIN VDE 0160).
4.6.1 Connection Cross-Sections and Cable Lengths
Connection Cross-Sections
The connection cross-sections for the input power connection, motor connection,
and cabinet grounding for your cabinet unit are specified in the tables provided in
the "Technical Data" section.
Cable Lengths
The following table shows the maximum permissible cable lengths (with output filter
(option L08) and without output filter) for standard cable types or cable types
recommended by SIEMENS. Longer cables can only be used after consultation.
The cable lengths specified represent the actual distance between the cabinet unit
and the motor, taking into account parallel routing, current-carrying capacity, and
the cable-laying factor.
Table 4-1 Max. permissible cable lengths
Cabinet unit w/o output filter
Voltage Output Protoflex
EMC 3 Plus
Shielded cable
(e.g. Protodur NYCWY)
Unshielded cable
(e.g. Protodur NYY)
380 - 480 V 110 kW 300 m 200 m 300 m
380 - 480 V 132 - 560 kW 300 m 300 m 450 m
660 - 690 V 75 - 800 kW 300 m 100 m 150 m
with output filter
380 - 480 V 110 kW 300 m 300 m 450 m
380 - 480 V 132 - 560 kW 300 m
Not required up to 300
m
Not required up to
450 m
660 - 690 V 75 - 800 kW 300 m 200 m 300 m