4.9.7 EMERGENCY OFF Category 0; 230 V AC or 24 V DC (Option L57)
Description
EMERGENCY OFF category 0 for uncontrolled stop to EN 60 204. This function
involves disconnecting the cabinet from the supply via the line contactor bypassing
the electronics by means of a safety combination to EN 60 204-1. The motor then
coasts to a stop. To prevent the main contactor from switching under load, a pulse
block is triggered at the same time via an external fault. A restart is only possible
after the fault has been acknowledged. The operational status is indicated by
means of three LEDs.
In the factory setting, this version is set with a 230 V AC button circuit.
Connection
Table 4-22 Terminal X120 – connection for EMERGENCY OFF category 0, 230 V AC and
24 V DC
Terminal 230 V AC and 24 V DC button circuit
7
8
Loop in EMERGENCY OFF button from system side,
remove jumper 7-8
15
16
"On" for monitored start:
remove jumper 15–16 and connect button
17
18
Checkback "trip safety combination"
Max. connectable cross-section: 4 mm² (AWG 10)
Reconnection to the 24 V DC Button Circuit
When using the 24 V DC button circuit, you must remove the following jumpers at
terminal X120:
4-5, 9-10, and 11-14
You must also insert the following jumpers at terminal X120:
4-11, 5-10, and 9-14
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs) are
described in “Additional Operating Instructions” in the operating manual.