11/03 Operation
SINAMICS G150
Operating Manual
6-11
6.2.2.5 Drive Commissioning Menu
This option enables you to re-commission the drive from the main menu.
6.2.2.6 Device Commissioning Menu
In this menu, you can enter the device commissioning status directly. This is the
only way that you can reset parameters to the factory setting for example.
You can use this menu to create motor data sets in subsequent drive software
versions.
6.2.3 Operation via the Operator Panel (LOCAL Mode)
You activate the control keys by switching to LOCAL mode. If the green LED in the
LOCAL-REMOTE key does not light up, the control keys are not active.
6.2.3.1 Timeout Monitoring
Settings: MENU – Settings – Control Settings
Timeout monitoring (factory setting: 3000 ms)
The monitoring time continuously monitors communication between the operator
panel and drive.
If, when the drive is in LOCAL mode, no communication signal has been received
once the monitoring time has elapsed, the drive is stopped with OFF1 and fault
F1030 ("control priority monitoring: sign-of-life failure") is displayed.
6.2.3.2 LOCAL/REMOTE Key
Activate LOCAL mode: press the LOCAL key
LOCAL mode: LED lights up
REMOTE mode: LED does not light up: the ON, OFF, JOG, direction reversal,
faster, and slower keys are not active.