11/03 Commissioning
SINAMICS G150
Operating Manual
5-5
Basic Commissioning: Selecting the Motor Type
Motortype select.(IEC/NEMA)
xxxxxxxxxxxxxxxxxxxxxxxxxx
p0100 = 0: IEC [50 Hz / kW]
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Help Change OK
F2F1 F3 F4 F5
xxxxxxxxxxxxxxxxxxxxxxxxxxxx
p0100 : 0: IEC [50 Hz / kW]
1: NEMA [60 Hz / hp]
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Help î™” Cancel OK
F2F1 F3 F4 F5
In the first dialog screen, select the line frequency
and motor data in kW or hp.
Change the values with <F4>
Confirm the values with <F5>
Defined as follows:
0: line frequency 50 Hz, motor data in kW
1: line frequency 60 Hz, motor data in hp
With <F2> and <F3> you can select the possible
settings.
Press <F4> to abort motor selection
Press <F5> to confirm the setting.
p0100 Sel. Mot. IEC/NEMA
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Motor data
Back
p0304 MOT.V_Rated 400.0 V
p0305 MOT.I_Rated 405.0 A
p0307 MOT.P_Rated 235.0 kW
p0308 MOT.CosPhi_Rated 0.870
xxxxxxxxxxxxxxxxxxxxxxx
Help   Change OK
F2F1 F3 F4 F5
Entering motor data specified on the type plate
Change the values with <F4>:
A screen appears in which you can enter the
respective values.
Press <Back> to return to the previous dialog screen
Motor data
Back
p03089MOT.CosPhi_Rated 0.870
p03109MOT.f_Rated 50.0 Hz
p03119MOT.n_Rated 1485.0 min
-1
xxxxxxxxxxxx
Help  Change Continue
F2F1 F3 F4 F5
Once you have set the values, press <F5> to confirm
them. The confirmed values are displayed with a tick
9 behind the parameter number.
Once you have set and confirmed all the values,
press <F5> to continue with basic commissioning.
p03079MOT.P_Rated 235.0 kW
Bild 5-5 Selecting the motor type and entering the motor data