Commissioning 11/03
SINAMICS G150
5-6 Operating Manual
Basic Commissioning: Entering the Basic Parameters
Entering the parameters for basic
commissioning
p1070 Main setpoint (03)r4055[00] means:
In the factory setting, the main setpoint (p1070) is
defaulted by analog input 0 (parameter r4055[00]) o
n
the customer terminal block (node address 03).
Press <F3> and <F2> to select the basic
parameters.
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
F2F1 F3 F4 F5
Press <F4> to change the values:
The system displays a screen in which you can ente
r
the relevant values.
Press <F5> to continue.
Final confirmation
Confirm the basic parameters to save them.
Press <Back> to return to the previous dialog screen
Press <F5> to continue.
The entered basic parameters are permanently
stored and the necessary calculations for the control
are carried out.
Basic commisioning
Back
p1070 Main setpoint (03)r4055[00]
p1075 Additional setp. 0%
p1080 Minimum speed 0.000 min
-1
xxxxxxxxxxxxxxxxxxxxxxxxxxx
Help   Change Continue
F2F1 F3 F4 F5
p1082 Maximum Speed 1500.000 min-1
Basic commisioning
Back
p1120 RG.t_Ramp_Up 20.00 s
p1121 RG.t_Ramp-Down 30.00 s
p1135 RG.t_OFF3 30.00 s
F2F1 F3 F4 F5
Final confirmation
ttt
Help Back OK
Apply parameters permanently with OK
p1082 Maximum Speed 1500.000 min
-1
may cause the shaft to turn.
F2F1 F3 F4 F5
Please switch on the drive to start
Motor identification
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
motor identification.
xxxxxxxxxxxxxxxxxxxxxxxxxxxx
Warning: The motor conducts current and
Help Alarm Cancel
Motor identification
You activate this function by pressing the LOCAL
key (wait until the LED in the LOCAL key lights up)
and then ON.
If you abort the motor ID function (<F4>), the motor
control does not operate with the measured values
but with the motor characteristic values calculated
from the type plate data. The measurement
increases the control performance as deviations in
the electrical characteristic values are minimized on
account of deviations in the material properties and
manufacturing tolerances.
Help   Change Continue
Fig. 5-6 Basic commissioning – Further dialog screens, concluding with the motor ID