Diagnosis / Faults and Alarms 11/03
SINAMICS G150
10-14 Operating Manual
Reaction: NONE
Cause: Defective files detected on CompactFlash Card during startup.
Remedy: - Repair files
- Save parameters (p0977).
- Fault can be acknowledged after saving
Acknowl.: Immediate
A1100 CU: CompactFlash Card removed
Cause: The CompactFlash card (non-volatile memory) was removed during operation.
Caution:
The CompactFlash card must not be removed or inserted when the system is live.
Remedy: - Switch off the drive system.
- Reinsert the CompactFlash Card that is suitable for the plant.
- Switch the drive system back on.
F1105 CU: Insufficient memory
Reaction: OFF1
Cause: Too many functions, data sets or drives are configured on this control unit.
Remedy: - Change configuration on this control unit.
- Use a different control unit.
Acknowl.: Immediate
F1107 CU: Save to CompactFlash Card failed
Reaction: NONE
Cause: Unable to save data on CompactFlash Card.
- CompactFlash Card defective.
- Insufficient memory on CompactFlash Card.
Remedy: - Try again.
- Use another CompactFlash card.
Acknowl.: Immediate
F1110 CU: Only one SINAMICS G at a time may be operated at a Control Unit.
Reaction: NONE
Cause: More than one drive of type SINAMICS G is in operation with the control unit.
Remedy: Only one drive of type SINAMICS G is permitted.
Acknowl.: Immediate
F1111 CU: Drive types SINAMICS S/G cannot be combined at a CU
Reaction: NONE
Cause: The drive units SINAMICS S and G are operating together on one control unit.
Remedy: You may only operate equipment of one drive type on one CU.
Acknowl.: Immediate
F1205 CU: Time slice overflow
Reaction: OFF2
Cause: Insufficient processing time for existing topology.
Remedy: Reduce the number of axes or increase the sampling times.
Acknowl.: POWER ON
F1210 CU: Basic clock cycle does not match DRIVE-CLiQ clock cycle
Reaction: NONE
Cause: The parameter for selecting the basic clock cycle does not match the drive topology. Drives
connected to the same DRIVE-CLiQ port of the control unit have been assigned different
basic clock cycles.
See also: p0111
Remedy: The same basic clock must be selected for drives connected to one and the same. DRIVE-
CLiQ port of the CU (e.g. in series).
See also: p0111
Acknowl.: Immediate