Operation 11/03
SINAMICS G150
6-22 Operating Manual
Setting range: 0.0 ... 1000.0 ms
p4053
Smoothing time constant analog
inputs
Factory setting: 0.0 ms
Setting parameter for the time constant of the 1
st
order low-pass filter for the analog inputs.
r4055 Current per-unit input value Unit: %
Display the current input value of the analog input in %.
NOTE
In the factory setting and after basic commissioning, an input current of 20 mA is
equal to the main setpoint 100 % reference speed (p2000), which has been set to
the maximum speed (p1082).
Example: Changing Analog Input 0 from Current to Voltage Input –10 to +10 V
Set analog input 0 type to -10 ... +10 V
p4056 = 4
S5.0 = "V"
Current / voltage switchover
Set the current / voltage selector switch to "voltage" (V)
Fig. 6-10 Example: Setting analog input 0
F3505 – Fault: "Analog input cable breakage"
This fault is triggered when analog input type (p4056) is set to 3 (4 ... 20 mA with
open-circuit monitoring) and the input current of 2 mA has been undershot.
The fault value can be used to determine the analog input in question.
Example
TM: Analog I. Wire Break
FaultValue: 0000000003 00000003(hex)
Cause:
TM31.Wire break analog input
Remedy:
TM31.Check Cable. Anal.Input
xxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Back  
F2F1 F3 F4 F5
Component ID
3: Modul -A60
4: Modul -A61 (option)
0: Analog input 0: -X521:1/2
1: Analog input 1: -X521:3/4
Fig. 6-11 Fault screen