11/03 Output Terminals
SINAMICS G150
Operating Manual
8-9
Setting range: -1000.00 ... +1000.00 %
p4079[0]
Value x2 for the analog output
characteristic
Factory setting: 100.00 %
Setting for the x coordinate in % of the second point on the scaling characteristic.
Setting range: -20.000 ... +20.000 V or mA
p4080[0]
Value y2 for the analog output
characteristic
Factory setting: 20.000 mA
Setting for the y coordinate in V or mA of the second point on the scaling characteristic.
The unit is V when analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 1
and 2 are used.
The unit is mA when analog output 0 is set as a current output (p4076[0] = 0 / 2 / 3) and terminals X522:
3 and 2 are used.
Additional Setting Parameters for Analog Output 1 (AO1)
Setting range: -1000.00 ... +1000.00 %
p4077[1]
Value x1 for the analog output
characteristic
Factory setting: 0.00 %
Setting for the x coordinate in % of the first point on the scaling characteristic.
Setting range: -20.000 ... +20.000 V or mA
p4078[1]
Value y1 for the analog output
characteristic
Factory setting: 0.000 mA
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
The unit is V when analog output 1 is set as a voltage output (p4076[1] = 1 / 4) and terminals X522: 4
and 5 are used.
The unit is mA when analog output 1 is set as a current output (p4076[1] = 0 / 2 / 3) and terminals X522:
6 and 5 are used.
Setting range: -1000.00 ... +1000.00 %
p4079[1]
Value x2 for the analog output
characteristic
Factory setting: 100.00 %
Setting for the x coordinate in % of the second point on the scaling characteristic.
Setting range: -20.000 ... +20.000 V or mA
p4080[1]
Value y2 for the analog output
characteristic
Factory setting: 20.000 mA
Setting for the y coordinate in V or mA of the second point on the scaling characteristic.
The unit is V when analog output 1 is set as a voltage output (p4076[1] = 1 / 4) and terminals X522: 4
and 5 are used.
The unit is mA when analog output 1 is set as a current output (p4076[1] = 0 / 2 / 3) and terminals X522:
6 and 5 are used.