11/03 Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-27
A2030 Function generator: Physical address equals zero
Cause: The specified physical address has the value zero.
See also: p4812
Remedy: Set the physical address to a different value than zero.
See also: p4812
A2040 Function generator: Impermissible value for offset
Cause: Offset value greater than upper limit or less than the lower limit.
See also: p4826
Remedy: Change the offset accordingly.
See also: p4826, p4828, p4829
A2041 Function generator: Impermissible value for bandwidth
Cause: The set bandwidth is either too small or too large.
See also: p4823
Remedy: Check value for bandwidth and adapt if necessary.
See also: p4823
A2045 Function generator: Inconsistent limit values
Cause: The values for the upper and lower limits are inconsistent.
The value for the lower limit must always be less than the value for the upper limit.
See also: p4828, p4829
Remedy: Check the limit values and adjust if necessary.
See also: p4828, p4829
A2050 Trace: Unable to start
Cause: Trace already started.
See also: p4700
Remedy: Stop and, if necessary, restart the trace.
A2055 Trace: Trace duration too short
Cause: The value for the trace duration is too short. Minimum length = twice the value of the trace
cycle.
See also: p4720, p4721
Remedy: Check the value for the trace duration and adjust if necessary.
A2056 Trace: Trace cycle too small
Cause: The selected trace cycle is less than the set basic clock cycle 0 (p0110[0]).
See also: p0110, p4720
Remedy: Increase the value for the trace cycle.
A2060 Trace: Signal to be traced is missing
Cause: - You have not specified a signal to be traced.
- The specified signals are not valid.
See also: p4730, p4731, p4732, p4733
Remedy: - Specify a signal to be traced (p4730 ... p4733).
- Check whether the relevant signal can be traced.
A2061 Trace: Invalid signal
Cause: The selected signal is invalid. Possible causes:
- Specified signal does not exist
- Specified signal cannot be traced.
See also: p4730, p4731, p4732, p4733
Remedy: - Specify a signal to be traced (p4730 ... p4733).
- Check whether the signal can be traced.
A2062 Trace: Trigger signal invalid