11/03 Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-39
Remedy: - Reduce permanent load.
- Adapt duty cycle.
- Check rated currents of motor and power section.
See also: r0036, r0206, p0307
Acknowl.: Immediate
F30011 Power section: Line phase failure detected
Reaction: OFF1
Cause: Line phase failure detected by power section.
- Fuse in main power circuit.
Remedy: Check fuses in main power circuit.
Acknowl.: Immediate
F30012 Power section: Temperature sensor Heatsink Wirebreak
Reaction: OFF2
Cause: The connection to one of the heatsink temperature sensors in the power section is
interrupted.
See also: r0949
Fault value
(r0949):
Bit0: Module duct (electronic module)
Bit1: Intake air
Bit2: AC converter 1
Bit3: AC converter 2
Bit4: AC converter 3
Bit5: AC converter 4
Bit6: AC converter 5
Bit7: AC converter 6
Bit8: DC converter 1
Bit9: DC converter 2
Remedy: Contact the manufacturer.
Acknowl.: Immediate
F30013 Power section: Temperature sensor Heatsink Short-circuit
Reaction: OFF2
Cause: The heat sink temperature sensor in the motor module is shorted.
Fault value
(r0949):
Bit0: Module duct (electronic module)
Bit1: Intake air
Bit2: AC converter 1
Bit3: AC converter 2
Bit4: AC converter 3
Bit5: AC converter 4
Bit6: AC converter 5
Bit7: AC converter 6
Bit8: DC converter 1
Bit9: DC converter 2
Remedy: Contact the manufacturer.
Acknowl.: Immediate
F30017 Power section: Hardware current limit tripped too may times
Reaction: OFF2
Cause: The hardware current limit in the various phases (see A30031, A30032, A30033) has tripped
too many times. The maximum permissible number of trips depends on the power section
type.
- Control incorrectly parameterized.
- Fault in motor or in power lines.
- Power lines exceed maximum permissible length.
- Motor load too high.
- Power section defective.