Diagnosis / Faults and Alarms 11/03
SINAMICS G150
10-44 Operating Manual
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy: Replace affected component.
Acknowl.: Immediate
F30832 Power section DRIVE-CLiQ: Telegram failure
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy: - Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
See also: p9916
Acknowl.: Immediate
F30833 Power section DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy: - Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F30834 Power section DRIVE-CLiQ: Hardware defect
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy: Replace affected component.
Acknowl.: Immediate
F30835
F30836
Power section DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy: - Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F30837
F30838
Power section DRIVE-CLiQ: Hardware defect
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy: Replace affected component.
Acknowl.: Immediate
F30860 -
F30871
CU DRIVE-CLiQ: Data transfer faulted / Telegram faulted
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy: - Check cabinet design and cabling for EMC conformity.
- Replace affected component.
Acknowl.: Immediate
F30872
F30873
CU DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause: Reserved for later use.
Remedy: Reserved for later use.
Acknowl.: Immediate