Diagnosis / Faults and Alarms 11/03
SINAMICS G150
10-52 Operating Manual
F35883 CU DRIVE-CLiQ: Hardware defect
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy: - Replace Control Unit.
Acknowl.: Immediate
F35884 CU DRIVE-CLiQ: Redundancy link error
Reaction: OFF2
Cause: Reserved for later use.
Remedy: Reserved for later use.
Acknowl.: Immediate
F35885 CU DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy: - Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F35886 CU DRIVE-CLiQ: Data transfer faulted
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy: - Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F35887
F35888
CU DRIVE-CLiQ: Hardware defect
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy: Replace Control Unit.
Acknowl.: Immediate
F35889 CU DRIVE-CLiQ: Data transfer faulted
Reaction: OFF2
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy: - Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
Acknowl.: Immediate
A35890 CU DRIVE-CLiQ: Connection setup
Cause: DRIVE-CLiQ communication between control unit and at least one other component is
defective.