Device Overview 11/03
SINAMICS G150
2-8 Operating Manual
Type Plate Data (from Type Plate on Previous Page)
Table 2-2 Type plate data
Specification Value Explanation
Input
3AC
380 – 480 V
239 A
Three-phase connection
Rated input voltage
Rated input current
Output
3AC
0 – 480 V
210 A
Three-phase connection
Rated output voltage
Rated output current
Temperature range
0 -40 °C Ambient temperature range within which the cabinet unit can
operate under 100 % load
Degree of protection
IP20 Degree of protection
Duty class
I I: Duty class I to EN 60146-1-1 = 100 % (continuously)
(with the specified current values, the cabinet unit can operate
continuously under 100 % load)
Cooling method
AF A: coolant: air
F: circulation method: forced cooling, drive unit (fan) in the
device
Weight
Weight of the cabinet unit
Explanation of the Option Short Codes
Table 2-3 Explanation of the option codes
Version
A C
Input options
L00 Radio interference suppression filter, limit class A1 (TN, TT systems) • −
L13 Main contactor (for currents < 800 A) • −
L22 Without line reactor in power range P < 500 kW (available soon) • •
L23 Line reactor u
k
= 2 % for P > 500 kW • •
L26 Main circuit-breaker (incl. fuses/circuit-breakers) • −
Output options
L08 Output filter • −
Input and output options
M70 EMC shield bus • •
M75 PE busbar • •