11/03 Maintenance and Servicing
SINAMICS G150
Operating Manual
11-9
Upgrading the Firmware for the Cabinet Unit Components
Select the node number of the power section
The node number of the power section is "2".
p7828 = 3
p7828 = 2
Access level "Expert"
Set the "Expert" access level on the operator panel
<Key pushbutton> - <Access level> - Enter the activation code
"47"
p7829 = 1
POWER ON
p7829 = 1
Upgrade the firmware
This process lasts a few minutes. It has been completed
successfully when p7829 automatically switches to "0".
Select the node number of the customer terminal block
The node number of the customer terminal block (-A60) is "3".
Fault during the upgrade
Faults that occur while the firmware is being upgraded are indicated by fault F1005 and a
fault value.
Upgrade the firmware
This process lasts a few minutes. It has been completed
successfully when p7829 automatically switches to "0".
POWER ON
To activate the new firmware, switch the power supply off and
then on.
Fig. 11-2 Upgrading the cabinet unit firmware
NOTE
Once the firmware has been upgraded, the firmware for the operator panel must
also be upgraded.