11/03 Technical Data
SINAMICS G150
Operating Manual
12-7
Table 12-8 Version A, 380 V – 480 V, part 3
Category Unit
Order no. 6SL3710- 1GE37-5AA0 1GE38-4AA0 1GE41-0AA0
Rated motor output kW 400 450 560
Rated connection voltage V 3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current A 785 883 1034
Rated output current A 745 840 985
Base load current A 725 820 960
Power loss kW 9.6 10.1 14.4
Cooling air requirement m³/s 0.78 0.78 1.48
Sound pressure level at 50/60
Hz
dB(A) 70/73 70/73 72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 300
2 x (800)
4 x 240
4 x (600)
M12 (2 holes)
4 x 150
4 x (400)
8 x 240
8 x (600)
M12 (4 holes)
4 x 185
4 x (500)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 300
2 x (800)
4 x 240
4 x (600)
M12 (2 holes)
4 x 150
4 x (400)
4 x 240
4 x (600)
M12 (2 holes)
4 x 185
4 x (500)
6 x 240
6 x (600)
M12 (3 holes)
Protective earth connection
Fastening screw
M12
(10 holes)
M12
(16 holes)
M12
(18 holes)
Approx. weight (standard
version)
kg 865 1075 1360
Dimensions (w x h x d) mm 1200 x 2000 x 600 1200 x 2000 x 600 1600 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 475
800
4
3NE1 448-2
850
3
Protective device
Circuit-breaker
Protective device
Circuit-breaker