11/03 Electrical Installation
SINAMICS G150
Operating Manual
4-39
connected (x = 1, 2, ...6). The limit values can be programmed by the user for each
channel.
In the factory setting, the measurement channels are divided into two groups of
three channels. With motors, for example, three PT100 can, therefore, be
monitored in the stator windings and two PT100 in the motor bearings. Channels
that are not used can be masked out using appropriate parameter settings.
The output relays are integrated in the internal fault and warning train of the
cabinet unit. The messages can also be picked up by the customer via two spare
fault signaling relays. Two user-programmable analog outputs are also available
(0/4 to 20 mA and 0/2 to 10 V) for integration in a higher-level controller.
Connection
Table 4-32 Terminal block -A1-A140 – connection for evaluation unit PT100 resistors
Terminal Designation Technical data
T11-T13 90 – 240 V AC/DC; PT100; sensor 1; group 1
T21-T23 90 – 240 V AC/DC; PT100; sensor 2; group 1
T31-T33 90 – 240 V AC/DC; PT100; sensor 3; group 1
T41-T43 90 – 240 V AC/DC; PT100; sensor 1; group 2
T51-T53 90 – 240 V AC/DC; PT100; sensor 2; group 2
T61-T63 90 – 240 V AC/DC; PT100; sensor 3; group 2
51/52/54 90 – 240 V AC/DC
relay output limit value group 1 reached; (two-way
contact)
61/62/64 90 – 240 V AC/DC
relay output limit value group 2 reached; (two-way
contact)
Ground _ OUT 1
U1 OUT 1
I1 OUT 1
0/4 – 20 mA
0/2 – 10 V
analog output Out 1; sensor group 1
Ground _ OUT 2
U2 OUT 2
I2 OUT 2
0/4 – 20 mA
0/2 – 10 V
analog output Out 2; sensor group 2
Max. connectable cross-section: 2.5 mm² (AWG 12)
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs) are
described in "Additional Operating Instructions" in the operating manual.