Operation 11/03
SINAMICS G150
6-8 Operating Manual
List of Signals for the Operation Screen
Table 6-1 List of signals for the operation screen
Signal Parameter Short name Unit Scaling (100 % = ...)
(see Table 6-2)
Factory Setting (entry no.)
Speed setpoint upstream of ramp
generator (1)
r1114 N_SET 1/min p2000
Output frequency (2) r0024 F_OUT Hz Reference frequency
Output smoothed (3) r0032 P_ACT kW r2004
DC link voltage smoothed (4) r0026 VDC V p2001
Actual speed smoothed (5) r0021 N_ACT 1/min p2000
Absolute actual current smoothed (6) r0027 I_ACT A p2002
Motor temperature (7) r0035 T_MOT °C Reference
temperature
Converter temperature (8) r0037 T_LT °C Reference
temperature
Actual torque smoothed (9) r0031 M_ACT Nm p2003
Converter output voltage smoothed (10) r0025 V_OUT V p2001
For diagnostic purposes
Speed setpoint smoothed r0020 N_SET 1/min p2000
Control factor smoothed r0028 % Reference control
factor
Field-producing current component r0029 A p2002
Torque-producing current component r0030 A p2002
Converter overload
Degree of thermal overload
r0036 % 100 % = Shutdown
Speed setpoint downstream of filter r0062 N_ACT 1/min p2000
Actual speed after smoothing r0063 N_ACT 1/min p2000
Control deviation r0064 1/min p2000
Slip frequency r0065 Hz Reference frequency
Output frequency r0066 Hz Reference frequency
Output voltage r0072 V_ACT V p2001
Control factor r0074 % Reference control
factor
Torque-producing actual current r0078 A p2002
Actual torque value r0080 Nm p2003
For further diagnostic purposes
Fixed speed setpoint active r1024 1/min p2000
Active motor potentiometer setpoint r1050 1/min p2000
Resulting speed setpoint r1119 1/min p2000
Speed controller output r1508 Nm p2003
I component of speed controller r1482 Nm p2003
PROFIBUS setpoint r2050 1/min p2000
Analog input 0 [V, mA] r4052[0] V, mA V: 100 V
mA: 100 mA
Analog input 1 [V, mA] r4052[1] V, mA V: 100 V
mA: 100 mA
Analog input 0, scaled r4055[0] % V: 10 V
mA: 20 mA
Analog input 1, scaled r4055[1] % V: 10 V
mA: 20 mA