Accessories
8.12 dv/dt filter plus VPL
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
161
Article number JTA: TEF1203
Maximum voltage rise at motor ter-
1)
< 500 V/μs < 500 V/μs < 500 V/μs
Maximum peak voltage at motor
terminals (phase to phase)
2)
1350 V 1350 V 1350 V
Maximum peak voltage at motor
terminals (phase to earth)
2)
1100 V 1100 V 1100 V
Maximum cable length filter - motor
350 m / 525 m 350 m / 525 m 350 m / 525 m
Rated terminal cross section (load
16 mm² 35 mm² 50 mm²
Rated terminal cross section (DC
3)
16 mm² 16 mm² 16 mm²
4)
5)
Connection Metrical (mm² / Nm)
Imperial (AWG / lbf.in)
Stripping length (mm)
Line / motor cable 16 / 1.2
6 / 11.0
35 / 2.5
2 / 22
70 / 6.0
2/0 / 53
DC link 16 / 1.2
6 / 11.0
16 / 1.2
6 / 11
16 / 1.2
6 / 11
Ground 16 / 1.2
6 / 11.0
35 / 2.5
2 / 22
70 / 10.0
2/0 / 86
Voltage rise according IEC/TS 60034-17
Under nominal DC link voltage
Short-circuit-proof wiring is required
Installing the filter in an enclosure is required
Higher ambient temperatures up to 60°C allowed with current derating at 40°C, in the range 40…50°C with 1.5% per 1K
and in the range 50…60°C with 1.9% per 1K