Technical data
6.5 400 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
91
Table 6- 18 PM240-2, IP20, frame size B, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE21-1UL0
6SL3210-1PE21-1AL0
6SL3210-1PE21-4UL0
6SL3210-1PE21-4AL0
6SL3210-1PE21-8UL0
6SL3210-1PE21-8AL0
LO base load power 4.0 kW 5.5 kW 7.5 kW
LO base load input current 13.3 A 17.2 A 22.2 A
LO base load output current 10.2 A 13.2 A 18.0 A
HO base load input current
HO base load output current 7.7 A 10.2 A 13.2 A
Fuse according to IEC
Fuse according to UL, class J
3NA3812 (32 A)
3NA3812 (32 A)
3NA3812 (32 A)
Required cooling air flow
Table 6- 19 PM240-2, PT, frame size B, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PE21-8UL0
6SL3211-1PE21-8AL0
LO base load input current
LO base load output current
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
3NA3812 (32 A)
1)
Required cooling air flow
Weight without filter 3.6 kg
Weight with filter 3.9 kg
approx. 0.16 kW through the heatsink