Technical data
6.5 400 V converters
Power Module PM240-2
94 Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 6- 24 PM240-2, PT, frame size D, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PE27-5UL0
6SL3211-1PE27-5AL0
LO base load power 37 kW
LO base load input current 70 A
LO base load output current 75 A
HO base load input current
HO base load output current 60 A
Fuse according to IEC
Fuse according to UL, class J
3NA3830 (100 A)
Power loss without filter
1)
1)
Required cooling air flow
Approx. 1 kW through the heatsink
Table 6- 25 PM240-2, IP20, frame size E, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE28-8UL0
6SL3210-1PE28-8AL0
6SL3210-1PE31-1UL0
6SL3210-1PE31-1AL0
LO base load input current
LO base load output current
HO base load input current
HO base load output current 75 A 90 A
Fuse according to IEC
Fuse according to UL, class J
3NA3832 (125 A)
3NA3836 (160 A)
Power loss without filter
Power loss with filter 1.30 kW 1.67 kW
Required cooling air flow 83 l/s 83 l/s