Technical data
6.5 400 V converters
Power Module PM240-2
94 Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 6- 24 PM240-2, PT, frame size D, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PE27-5UL0
6SL3211-1PE27-5AL0
LO base load power 37 kW
LO base load input current 70 A
LO base load output current 75 A
HO base load power
30 kW
HO base load input current
62 A
HO base load output current 60 A
Fuse according to IEC
Fuse according to UL, class J
3NA3830 (100 A)
100 A
Power loss without filter
1.09 kW
1)
Power loss with filter
1.10 kW
1)
Required cooling air flow
55 l/s
Weight without filter
20 kg
Weight with filter
22 kg
1)
Approx. 1 kW through the heatsink
Table 6- 25 PM240-2, IP20, frame size E, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE28-8UL0
6SL3210-1PE28-8AL0
6SL3210-1PE31-1UL0
6SL3210-1PE31-1AL0
LO base load power
45 kW
55 kW
LO base load input current
86 A
104 A
LO base load output current
90 A
110 A
HO base load power
37 kW
45 kW
HO base load input current
78 A
94 A
HO base load output current 75 A 90 A
Fuse according to IEC
Fuse according to UL, class J
3NA3832 (125 A)
125 A
3NA3836 (160 A)
150 A
Power loss without filter
1.29 kW
1.65 kW
Power loss with filter 1.30 kW 1.67 kW
Required cooling air flow 83 l/s 83 l/s
Weight without filter
26.4 kg
26.4 kg
Weight with filter
28.4 kg
28.4 kg