Technical data
6.5 400 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
93
Table 6- 22 PM240-2, IP20, frame size D, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE23-8UL0
6SL3210-1PE23-8AL0
6SL3210-1PE24-5UL0
6SL3210-1PE24-5AL0
6SL3210-1PE26-0UL0
6SL3210-1PE26-0AL0
LO base load power 18.5 kW 22 kW 30 kW
LO base load input current 36 A 42 A 57 A
LO base load output current 38 A 45 A 60 A
HO base load input current
HO base load output current 32 A 38 A 45 A
Fuse according to IEC
Fuse according to UL, class J
3NA3822 (63 A)
3NA3824 (80 A)
3NA3830 (100 A)
Power loss without filter
Required cooling air flow
Table 6- 23 PM240-2, IP20, frame size D, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE27-5UL0
6SL3210-1PE27-5AL0
LO base load input current
LO base load output current
HO base load input current
HO base load output current 60 A
Fuse according to IEC
Fuse according to UL, class J
3NA3830 (100 A)
Power loss without filter
Power loss with filter 1.10 kW
Required cooling air flow 55 l/s