EasyManua.ls Logo

Siemens SINAUT ST7 - 2.1 Design of the MD2 Modem

Siemens SINAUT ST7
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Introduction to the SINAUT ST7 system
1.3 SINAUT TIM communication modules
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
21
TIM 3V-IE Advanced
Message memory on TIM
Number of messages
Buffered
32,000 messages
no
Transmission protocols (RS-232)
Selectable protocols
SINAUT ST7
SINAUT ST1
Mode with dedicated line/wireless network
SINAUT ST7 protocol
SINAUT ST1 protocol
- Polling
- Polling with time slots
- Multi-master polling with
time slots
- Polling
- Polling with time slots
Mode in dial-up network
SINAUT ST7 protocol
GPRS/MSC tunnel on the basis of the
SINAUT ST7 protocol
SINAUT ST1 protocol
Spontaneous
Spontaneous
Spontaneous
Asynchronous character format
SINAUT ST7 protocol, polling or
spontaneous
SINAUT ST7 protocol,
multi-master polling
SINAUT ST1 protocol, polling
SINAUT ST1 protocol, spontaneous
10 or 11 bits
10 bits
11 bits
10 or 11 bits
Hamming distance d
SINAUT ST7 protocol
SINAUT ST1 protocol
4
4
Ethernet
Protocol TCP/IP transport protocol
Communication services
SINAUT ST7 using S7 communication
SINAUT ST7 via MSC tunnel
PG communication
Number of connections
S7 communication
MSC connections
Total number of simultaneously operable
productive connections (S7 + MSC)
Also:
PG communication
max. 20
max. 1 (only as MSC station)
max. 21
max. 2
1)
The MPI ports of the S7-300-CPU can be used with the following CPU types:
All variants of the CPU 312, CPU 312C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP