2.24 Command Processing
335
7UT613/63x Manual
C53000-G1176-C160-2
The plus sign indicated in the indication is a confirmation of the command execution:
The command output has a positive result, as expected. A minus sign means a neg-
ative, i.e. an unexpected result; the command was rejected. Figure 2-126 shows an
example in the operational indications command and feedback of a positively run
switching action of the circuit breaker.
The check of interlocking can be programmed separately for all switching devices and
tags that were set with a tagging command. Other internal commands such as over-
riding or abort are not tested, i.e. are executed independently of the interlockings.
Figure 2-126 Example of an operational indication for switching circuit breaker 52
Standard Interlock-
ing
The standard interlocking includes the checks for each switchgear which were set
during the configuration of inputs and outputs, see SIPROTEC 4 System Description.
An overview for processing the interlocking conditions in the relay is shown in Figure
2-127.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals