EasyManuals Logo

Siemens SIPROTEC 7UT63 series User Manual

Siemens SIPROTEC 7UT63 series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #401 background imageLoading...
Page #401 background image
3.3 Commissioning
401
7UT613/63x Manual
C53000-G1176-C160-2
• Phase angle measurement for measuring location M1 with test current:
Check the phase angle under measurement values → secondary → phase
angles of side 1 of the protected object. All angles are referred to I
L1M1
. The follow-
ing values must result approximately for a clockwise phase rotation:
Ï•
L1 M1
≈ 0°
Ï•
L2 M1
≈ 240°
Ï•
L3 M1
≈ 120°
If the angles are wrong, reverse polarity or swapped phase connections on measur-
ing location M1 may be the cause.
– Switch off the test source and the protected object (shut down the generator) and
earth it.
– Re-check the plant connections to the device and the test arrangement and
correct them.
– Repeat test and re-check the current angles.
• Phase angle measurement for measuring location M2 with test current:
Check the phase angle under measurement values → secondary → phase
angles of measuring location M2 of the protected object. All angles are referred to
I
L1M1
.
Consider that always the currents flowing into the protected object are defined as
positive: That means that, with through-flowing in-phase currents, the currents
leaving the protected object at measuring location M2, have reversed polarity (180°
phase displacement) against the corresponding in-flowing currents at measuring lo-
cation M1.
Exception
: With transverse differential protection, the currents of the corresponding
phase have equal phase!
For clockwise phase rotation and without phase displacement, the angles should
be approximately:
Ï•
L1 M2
≈ 180°
Ï•
L2 M2
≈ 60°
Ï•
L3 M2
≈ 300°
When measuring across a power transformer, approximately the values according
to Table 3-28 result for clockwise phase rotation:
Table 3-28 Displayed phase angle dependent on the protected object (three-phase)
1)
Angles are valid if the high voltage side is defined as side 1, otherwise read 360° minus the
stated angle
Protected Object Generator/Motor/
Busbar/Line
Transformer with Vector Group Numeral
1)
Phase Angle ↓ 01234567891011
Ï•
L1M2
180° 180° 150° 120° 90° 60° 30° 0° 330° 300° 270° 240° 210°
Ï•
L2M2
60° 60° 30° 0° 330° 300° 270° 240° 210° 180° 150° 120° 90°
Ï•
L3M2
300° 300° 270° 240° 210° 180° 150° 120° 90° 60° 30° 0° 330°

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals