A simulated value (from a preset selection, or a value set by customer) can be set to test the
functioning of t
he mA connections during commissioning or maintenance of the device. The
range is 3.55 mA to 22.8 mA.
P$P$P$P$P$P$
Normal operation Upper saturation limit (factory
se
tting)
Lower fault current (factory setting) Upper fault current (factory set‐
ting)
Lower saturation limit (factory setting)
Note
Simulat
ed current output
The simulated current output value in󹪞uences output to the control system.
In general, to simulate current output:
1
. Run the "Loop test wizard" from the menu "Maintenance and diagnostics > Loop test" on the
device (or from the Device menu in SIMATIC PDM).
Select a preset mA value, or enter a custom value. (Custom value can be entered by
selecting "User" option on device, or "Other" option in PDM.)
2. Start the loop test.
3. When you are ready to end the simulation, stop the loop test by exiting the wizard.
The device returns to the actual output value.
8.5.1 Simulation - Process value (Operating chapter)
Process value simulation
Process value simulation is an iterative process whereby parameters are adjusted and
corresponding results are displayed. Process values can be simulated using a remote
Operating
8.5Simulation
SITRANS LR500 series with mA/HART
90 Operating Instructions, 03/2024, A5E51099898-AA