Parameterizing Steps 05.2006
6SE7087-2JD60 Siemens AG
9-26 Operating Instructions SIMOVERT MASTERDRIVES
87654321
Setpoint source
MASTERDRIVES VCOP1S and fixed setpoints (P368=7)
- s71 -
KK0046
KK0045
KK0047
KK0048
KK0040
Act.FSetp
Active FSetp
r420
P443.B (40)
KK
Src Main Setpoint
P486.B (40)
KK
Src T setpoint
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
FSetp
Bit 3
P418.B
FSetp
Bit 2
P417.B
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
KK0042
KK0041
KK0043
KK0044
(for T control)
Fixed setpoint1
P401.F
Fixed setpoint2
P402.F
Fixed setpoint3
P403.F
Fixed setpoint4
P404.F
Fixed setpoint5
P405.F
Fixed setpoint6
P406.F
Fixed setpoint7
P407.F
Fixed setpoint8
P408.F
in %
in Hz
Fixed
setpoints
Sheet [290]
Terminal strip
Sheet [90]
If used as digital inputs, the parameters
P651.B, P652.B, P653.B and P654.B must
be set to 0!
If used as digital outputs, B10 to B14 must
not be wired.
*
)
from sheet [200]
to sheet [180]
to sheet[316.1]
to sheet[320.1]
N
M
n959.89 = 4
If P366 = 2
P590 = B0012
P651 = B0000
P652 = B0000
P653 = B0107
/5
/4
/3
/2
/1
B0014
P653.1 (0)
B
B0012
P652.1 (104)
B
B0010
P651.1 (107)
B
M24
P24
-X101
B0104
B0107
Operation
0=fault
*
)
*
)
1=operation
No fault
*
)
P590 (14)
B
Src BICO DSet
See P049.4
FSetp
Bit 1
P581.B
FSetp
Bit 0
P580.B
(for T control)
(for n/f control or v/f control)