Features
20
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
Keys Description
1 … 4 Operating access code input (level 2, programming, system test, etc.)
è When operating access level 2 is selected, if the code is entered again, the system returns to the level 1, without waiting
for the end of the 4 minutes timeout
5
t sounders by successive pressing:
– 1st pressing: silence sounders
– 2nd pressing: restart sounders etc…
è Operating access level required for this operation = level 2 (silence sounders is not possible during pre-discharged
warning time)
6
è Operating access level required for this operation = level 1 or 2 or 2 only (according to programming)
è If a Repeater Terminal is connected to the XC10, and if option 61 step 02 is selected, silence buzzer on XC10 silences
also buzzer on repeater
7
of the system. Reset is not possible
– during pre-discharged warning time, emergency stop and flooding time
– if buzzer and/or sounders are not silenced
– if manual release button and/or discharged contact are not reset (according to programming)
è Operating access level required for this operation = level 2
2) Fault reset
è Operating access level required for this operation = level 2
8
Mode of operating, by successive pressing:
– 1st pressing: automatic blocked
– 2nd pressing: automatic and manual blocked
– 3rd pressing: normal mode
è Operating access level required for these operations = level 2
9
Led and buzzer test (duration = 6 seconds)
All led indicators are activated and the buzzer sounds continuously (during the first three seconds, all the segments of the
display are activated, then the SW version is displayed)
è Operating access level required for this operation = level 1
10
Disable / Enable by successive pressing:
– 1st pressing: actuators are disabled
– 2nd pressing: sounders and actuators are disabled
– 3rd pressing: fire controls are disabled
– 4th pressing: all is disabled
– 5th pressing: all is enabled
è Operating access level required for these operations = level 2
11
Disable / Enable by successive pressing:
– 1st pressing: RT-fault is disabled
– 2nd pressing: RT-fault is enabled / RT-alarm is disabled
– 3rd pressing: RT-fault and RT-alarm are disabled
– 4th pressing: all are enabled
è Operating access level required for these operations = level 2
12
Disable / Enable by successive pressing (not possible in case of fault or
– 1st pressing: zone 1 is disabled
– 2nd pressing: zone 1 is tested
– 3rd pressing: zone 1 is in normal condition
è Operating access level required for these operations = level 2
13
Disable / Enable by successive pressing (not possible in case of fault o
– 1st pressing: zone 2 is disabled
– 2nd pressing: zone 2 is tested
– 3rd pressing: zone 2 is in normal condition
è Operating access level required for these operations = level 2
14
Disable / Enable by successive pressing (not possible in case of fault
– 1st pressing: zone 3 is disabled
– 2nd pressing: zone 3 is tested
– 3rd pressing: zone 3 is in normal condition
è Operating access level required for these operations = level 2
15
Disable / Enable by successive pressing (not possible in case of fault
– 1st pressing: manual release is disabled
– 2nd pressing: manual release is tested
– 3rd pressing: manual release is in normal condition
è Operating access level required for these operations = level 2