77
EN
– press the button
>
and select "1" (LPG)
– press the button
o
for at least 3 seconds to confirm the
modification. the value will stop flashing.
Procedure which MUST be carried out after:
–
gas conversion
–
changing the gas valve following a fault
–
changing the the electronic board following a fault.
– go into the parameter section (if not already there) by pressing
the buttons
<
and
o
(approximately 5 seconds) at the same
time until
“tS”
(installer) appears on the 2 digits of the display
which alternate with
“0.1”
(parameter number) and a
“2”
(set
value)
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "tS 4.9"
– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
– press the button
>
or
<
to set the value
at “49”
– press the button
o
to confirm the modification The value will
stop flashing
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "tS 7.0"
– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
– press the button
>
or
<
to set the value
“5”
– press the button
o
to confirm the modification The value will
stop flashing
– exit the parameter section by pressing and holding down the
buttons
<
and
o
at the same time
(approximately 5 seconds)
until the delivery temperature is displayed.
m
IMPORTANT
To complete this task the user
MUST
carry out the
following procedure.
Adjusting maximum gas pressure:
– press the button
s
until "SUMMER" mode
l
has been
selected
– turn the domestic hot water knob as far as it will go
r
– press and hold down the buttons
o
and
s
at the same time
for approximately 6 seconds until the message "Au" appears
on the display alternating with "to"
–
open one or more than one hot water tap
– the boiler will start up and the message
“P01”
will appear on
the display (Adjusting maximum gas pressure)
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
s
for approximately 2 seconds to confirm the value
which will then flash once.
Adjusting minimum gas pressure:
– press the button
o
twice, the message "P00" will appear on
the display
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
s
for approximately 2 seconds to confirm the value
which will then flash once