62
__________________________________________________________________________
7. Go to the Equations window on the right of the programmer window and enter the
equation:
The INPUT Opcode specifies when the self-test will run. For example, the
existing “Compare Day-of-Week value” INPUT Opcode could be used to
create a task that will execute every Sunday at 2:00am.
For the OUTPUT opcode, click on the Add button and select the
“Run Self-Test” option from the CC Input/Output window. Click on Next to
configure the scheduled self-test options:
i. Enter the point name of the TrueAlert Zone (SIGs) lists that will be tested
by the scheduled self-test. Contrary to a regular self-test, multiple SIGs
can be entered for testing in a scheduled self-test.
ii. In the Qualifier window, select the volume the test will be run at
normal or silent. Click on Next.
iii. A second Qualifier window appears and allows the user to choose
whether a failed device will trigger a trouble (select yes) or not (select
no).
Equation example:
[INPUTS]
WHEN DAY IS SUN
AND IF ANALOG = CONSTANT 2.000000 CNTS
A6 | Compare Analog | ANALOG | ANALOG | CURRENT HOUR
AND IF ANALOG = CONSTANT 0.000000 CNTS
A7 | Compare Analog | ANALOG | ANALOG | CURRENT MINUTE
[END INPUTS]
[OUTPUTS]
RUN_SELF_TEST L257 NORMAL NO
[END OUTPUTS]
8. Save the job with the new cutom control and download it to the FACP.
9. Enable the scheduled Self-Test at the Panel by accessing the pseudo point 503 and
setting it to ON.
10. Once the scheduled Self-Test has been enabled it will start to run at the designated time.
Note: Complex custom equations can be written with the Self-test wizard to set up one or more schedules
that will run the scheduled Self-test feature in the ES Fire Panel. See document 0574-849, ES Panel
Programmer’s Manual for details.
TrueAlert ES Appliance Self-Test , Continued
Scheduling a
Self-Test

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing

Related product manuals