53
3. Press the <ENTER> key on the Display/Action keypad. If the test is successful, the following
message displays.
_______________________________________________________________________________
Use the following procedure to test separately each of the TrueAlert Power Supply’s SLC lines.
Before you start this test, make sure you have already completed the procedure Accessing the
TrueNAC Voltage Drop Test.
1. Press the <NEXT> key on the Display/Action keypad. The following message displays.
2. Press the <ENTER> key on the Display/Action keypad. The following message displays.
3. Use the <NEXT> and <PREVIOUS> keys on the Display/Action keypad to change the SLC
channel.
4. Press the <ENTER> key on the Display/Action keypad. The following message displays.
5. To turn the horn on or off before performing the TrueNAC Voltage Drop Test, use the
<NEXT> and <PREVIOUS> keys to set the horn state.
Note: The horn can be turned off to prevent any disturbance during the TrueNAC Voltage Drop Test.
Horns that are turned on are set to high volume. If Horns are on, the panel will perform two passes one
with horns on and one with horns off. This is done to enhance measurement accuracy with A/V’s.
_______________________________________________________________________________
Continued on next page
TrueNAC Voltage Drop Test, Continued
114BTesting all TrueAlert
Power Supply’s
SLCs
115BTesting each
TrueAlert Power
Supply’s SLC
ALL TPS SLCs
TrueAlert TEST COMPLETED
CARD X, TRUEALERT POWER SUPPLY
<ENTER>=Select Channel
TPS CARD: X Channel: X
<ENTER>=Enable TrueNAC Test
TPS CARD: X Channel: X
<ENTER>=HORN ON